Abstract
The quasi local heat transfer coefficients of R22 and R407C in the coaxial counterflow condenser (20 mm ID) of a refrigerating vapour compression plant have been experimentally measured. The experimental conditions under which the heat transfer coefficients were determined reflect a typical working situation for small scale refrigeration systems. The plant runs with low mass fluxes of refrigerant within the range of 45.5–120 kg/m2/s. During the experimental tests the pressure at the inlet of the test condenser varies within a fixed range between 15.2 and 14.3 bar. The results illustrate that the R22 heat transfer coefficient is always greater than that of R407C. Furthermore, comparisons between the experimental data and the values predicted by means of the most credited literature relationships for gravity-driven condensation are reported.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.