Abstract

R-410A condensation heat transfer and pressure drop data are provided for a 5.0 mm O.D. microfin tube having 40 fins with 18 degree helix angle and 40 degree fin apex angle. Tests were conducted for a range of quality (0.2 ~ 0.8), mass flux (346 ~ 692 kg/m2s) and saturation temperature (45 ~ 55°C). Data are compared with smooth tube counterpart. It was found that both heat transfer coefficient and pressure drop increased as mass flux increased. The range of pressure drop penalty factor (1.83 ~ 2.62) was slightly larger than that of heat transfer enhancement factor (1.24 ~ 1.66). Data are compared with available heat transfer and pressure drop correlations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.