Abstract

An experimental investigation was performed to evaluate the condensation heat transfer characteristics for R32 and R410A inside four horizontal round tubes with 12.7 mm outer diameter. The saturation temperatures were 35 °C and 45 °C, the vapor qualities ranged from 0.2 to 0.8, and the mass flux ranged from 50 kg m−2 s−1 to 200 kg m−2 s−1. Different inside surface structures of the four tubes were smooth (ST), hydrophobic (HYD), herringbone (HB) and hydrophobic/herringbone (HYD/HB), respectively. Effects of mass flux, vapor quality, refrigerant and saturation temperature on condensation heat transfer in different tubes were discussed with the aid of flow pattern visualizations. Experimental results show that the heat transfer coefficient of R32 was higher than that of R410A due to different physical properties of the refrigerant. HB tube had the highest heat transfer coefficient at low vapor quality and HYD tube was the best at high vapor quality. The performance enhancement factors (PEF) of HB tube and HYD tube were better, ranging from 1.07 to 1.4 and from 1.02 to 1.31, respectively. However, as the composite of HB and HYD, the HYD/HB tube had the lowest overall performance, with the PEF ranged from 0.94 to 1.12. Additionally, the specific sensitivity factor (SSF) was used to evaluate the influence of various parameters on heat transfer and pressure drop.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.