Abstract
An EHV transformer's insulation structure must be designed to withstand the internal stresses generated during transients. Computer models are employed for predetermination of these stresses. This paper develops a detailed transformer model and solution method which represent the nonlinear, saturable characteristic of the magnetic core during transients. The resulting set of stiff nonlinear differential algebraic equations are solved by application of Gear's method. This paper describes the transformer model and the necessary set of equations based on linearization of the iron core's saturable magnetic characteristic at each time interval. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.