Abstract

An EHV transformer's insulation structure must be designed to withstand the internal electrical stresses generated during system transients. Computer models are employed for predetermination of these stresses. Part I of this paper developed a detailed transformer model and solution method representing the nonlinear, saturable characteristic of tire core during transients. The resulting set of stiff nonlinear differential algebraic equations are solved by application of Gear's method. Part II presents the verification of this methodology. This is accomplished by comparing the computed and measured response of a 765/345/34.5 kV 500 MVA autotransformer during energization and transient excitation.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.