Abstract

In the total energy consumption of the building, nearly 40% of energy is consumed by heating, ventilation and air conditioning (HVAC) system. Along with energy saving, it becomes a difficult task to maintain the acceptable thermal comfort and good indoor air quality by using conventional system alone. Present study aims to overcome these problems by integrating personalized ventilation with mixing ventilation system in an office room environment. Typical office cabin is considered and analyses are carried out in ANSYS-FLUENT to evaluate the performance of personalized ventilation system assisted with mixing ventilation system. A 3D computational model is developed and the velocity and temperature distribution around the occupant is obtained. For this analysis, the mixing ventilation and personalized ventilation supply temperatures are maintained at 18°C and 22°C while the corresponding flow rates are 60 l/s and 4 l/s respectively. The simulation results show that the vertical temperature profile and PMV-PPD indices based on Fanger’s thermal comfort model are in the acceptable range of occupant’s thermal comfort.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.