Abstract
A new method to calculate very fast transient over-voltages (VFTOs) in transformer windings has been presented. The applied algorithm uses a hybrid model which is a combination of the multi-conductor transmission line model (MTLM) and the single-transmission line model (STLM). The voltages at the end of each coil are calculated with the STLM model. Then, these values are used in the MTLM to determine the distributed over-voltages along the turns. Several representative curves with respect to time in transformer windings are illustrated. The maximums of over-voltage and electric field intensity generated in wire coils and in wire turns are also given. It is essential for transformer's insulation design.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.