Abstract

The reclosing time of a transmission line has a distinct influence on system stability. A new method of calculating the optimal reclosing time based on the transient energy function (TEF) is presented in this paper. It has been shown that an optimal reclosing time can be used to set the autoreclosing device so that the system stability or power-transfer capability can be significantly improved. Though power-system TEF is based on classical models, the results from simulation studies of a real system (46 generators and 230 buses) with complex models show that the optimal reclosing time calculated using TEF can be used effectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.