Abstract

Transmission tower modelling is very important to assess the electromagnetic transient caused by lightning strikes in power systems. In this context, conventional tower models are very well studied in the literature. However, there are few studies on tall transmission towers which have been receiving great attention recently due to their own characteristics. Tall transmission towers are built on river crossings and/or over dense forest canopy to reduce environmental impact in these areas. In this paper, the voltage surge caused by an incidentlightning at the top of the conventional and tall towers are determined. For both structures, a lumped electric circuit approximated by Vector Fitting technique is proposed which takes into account the tower-footing grounding system buried in different homogeneous soils. The results show a clear difference in the time domain voltage response for the conventional and tall transmission towers which is more pronounced as the soil resistivity increases and/or the tower becomes taller.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.