Abstract

Refrigeration oil is used for lubrication, sealing and cooling in refrigerant compressors, and mixing of the oil with refrigerant has great influences on compression characteristics in the compressors. In the past there were some studies in which the effect of the oil on the compressor performance was analyzed theoretically, but most of them did not discuss well the propriety of the oil treatment in the analysis. In this study, we developed the mathematical compressor model including the effect of the oil on leakage, heat transfer and flow resistance in vane compressors and examined the influence of the ways of treating the oil on the calculated results. When the model employed a quality of two-phase leakage flow equal to that in the compression chamber and a coefficient of heat transfer reflecting thermophysical properties of the oil and the refrigerant, it showed better agreement with experimental results.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.