Abstract
Chlorination is an effective disinfection method of drinking water treatment. Optimizing this process poses certain challenges, as the objectives of reaching the required disinfection effect and limiting the formation of disinfection by-products must be met simultaneously. These need adjusting the chlorine dosage in real time to cope with fluctuations in water quality and maintaining a free chlorine residual at the clear-water reservoir outlet that does not exceed regulatory limits. This paper proposes a composite control scheme that combines disturbance observer (DOB) and model predictive control (MPC) to meet the aforementioned objectives. MPC is employed for the feedback control of post-chlorine dosage, and DOB is adapted to monitor fluctuations in influent water quality. The estimated value from the DOB is applied in the feed-forward control of post-chlorine dosage. Both simulation and experimental results demonstrate that the proposed DOB-MPC composite control scheme provides a better disturbance rejection effect against fluctuations in influent water quality than MPC-only and PID-only control schemes, and it can effectively stabilize the quality of treated water.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.