In this paper, we present the electrical and mechanical behaviour of Cross-Linked Polyethylene (XLPE), used as electrical insulation in high voltage cables, under thermal ageing. Continuous accelerated thermal ageing tests on 18/30kV XLPE cable samples were performed during 2000 hours at four temperatures ranging from 80 °C to 140 °C. Every 200 hours, we measured the partial discharge threshold voltage, the dielectric loss factor and the dielectric constant. The mechanical properties (elongation at fracture and tensile strength) were measured before and after thermal ageing. The obtained results show that the thermal ageing affects greatly the properties of the material.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.