Abstract

This paper presents the application of a hybrid active power filter for reactive and harmonic compensation at the level of Medium Voltage (MV) of an electrical network of an industrial plant. It is considered as control algorithm, the application of the d-q theory and performing the current measuring in the system, establishing a feedback control loop (feedback). It is analyzed a hybrid topology called Shunt Hybrid Active Power Filter SHAPF. This proposal uses an existing capacitor bank, transformed into a passive filter, and connected in series with the Active Filter to build a hybrid filter in which the compensation supplement is made by the active filter. We analyze different scenarios of operation. The topology has very good performance under steady state and transient.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call