Abstract

A combined system of shunt passive and small rated series active filters, as well as its operating principle and steady compensation characteristics, was previously presented by the authors (1988). The combined system can greatly reduce problems of using only the shunt passive or shunt active filters and is suitable for harmonic compensation for large VA-rated loads in power systems. Transient compensation characteristics and the stability of the system are discussed and analyzed theoretically and experimentally in detail. A control method enables the combined system to be applied to cycloconverter compensation. Some results obtained with the experimental model are presented to demonstrate and confirm the method's validity. >

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.