Abstract

Comparison tests have been conducted on a flat-oval evaporator with a longitudinal replenishment of the evaporation zone with a working fluid (ELR) measuring 110 × 50.5 × 10 mm3 and a flat disk-shaped evaporator with opposite replenishment (EOR) 50 mm in diameter and 19 mm in thickness. The evaporators have been tested as parts of copper-water loop heat pipes (LHPs) with identical design parameters, with a heat source of 40 × 40 mm2 at a heat sink temperature of 40 °C. It is shown that an LHP with an ELR has a significantly lower operating temperature in the whole range of heat loads. The maximum heat load of the device with an ELR was 800 W at an evaporator temperature of 109.5 °C and with an EOR it was 600 W at a temperature of 121.1 °C. The corresponding thermal resistances of the evaporators were 0.025 °C/W and 0.046 °C/W. At a nominal heat load of 300 W the ELR temperature was 70.2 °С and the EOR temperature 87.4 °С. The devices were designed for use in energy-efficient cooling systems for high-power electronics. A computer simulation of heat exchange processes in the evaporators was carried out taking into account parasitic heat flows into the compensation chamber.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.