Abstract

This paper establishes the linearized Phillips-Heffron model of a power system equipped with UPFC and demonstrates the application of the model in analyzing the damping effect of the UPFC and designing UPFC based stabilizer to improve power system oscillation stability. A comprehensive approach to the design of UPFC based stabilizer (power flow control, DC-voltage regulator and damping controller) is presented. In this case, the multi-machine power system with UPFC is studied and an example of power system is presented. It is shown that the DC voltage contributes negative damping to power system oscillations, which is confirmed by both eigenvalue computation and nonlinear simulation. To counterattack the negative damping effect due to the DC voltage regulator, UPFC based stabilizer is designed and its effectiveness is demonstrated by both eigenvalue computation and nonlinear simulation. Then the effects of UPFC and PSS on power systems are compared. Simulation results show that the performance of UPFC based stabilizer on damping of power system is better than PSS.

Highlights

  • The Unified Power Flow Controller (UPFC) is a FACTS device which can control power system parameters such as terminal voltage, line impedance and phase angle[1,2]

  • We can see that: Power flow controller: The UPFC is installed in an nmachine power system between node 1 and node 2[6,7]

  • Case Study we consider a three machine power system with UPFC shown in Fig. 3, parameters of which are given below

Read more

Summary

INTRODUCTION

The Unified Power Flow Controller (UPFC) is a FACTS device which can control power system parameters such as terminal voltage, line impedance and phase angle[1,2]. The primary function of the UPFC is to control power flow on a given and voltage at the UPFC bus This is achieved by regulating the controllable parameters of the systems, line impedance, phase angle and voltage magnitude. A comprehensive approach to the design of UPFC based stabilizer (power flow control, DC-voltage regulator and damping controller) is presented. In this case, the multi-machine power system with UPFC is studied and an example of power systems is presented. To counterattack the negative damping effect due to the DC voltage regulator, UPFC based stabilizer is designed and its effectiveness is demonstrated by both eigenvalue computation and nonlinear simulation. We compare the effect of UPFC and PSS on power systems

MATERIALS AND METHODS
RESULTS AND DISCUSSION
CONCLUSION