Abstract

The paper presents a comparison of partial discharge (PD) measurements taken on 140 large power transformers using radio-influence voltage (RIV) meters calibrated in pV according to NEMA 107 Standard and also with the aid of wide-band and narrow-band PD detectors calibrated in pC according to IEC Publication 270. Results are presented in the form of pC/?V ratios and compared to data from the literature. In conclusion the RIV measuring technique is considered inappropriate for PD measurements on power transformers, although it can be employed to detect the presence of the discharges.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.