Abstract
Five selective-black-metal-plate experimental air heaters with and without transpiration were designed, fabricated, and tested to compare their technical merits. All were 61 cm × 61 cm (2ft × 2ft), double-glazed with low-iron glass, and those with transpiration contained an additional Teflon film to form a plenum above the absorber plate. The configurations were (i) a reference collector with flow on back only, (iia) a transpired slotted plate, (iib) a transpired micro-perforated plate, (iii) a corrugated plate with flow on back, and (iv) a transpired slotted corrugated plate. The results show the magnitude of technical improvement that can be obtained through the slotting, perforating, and corrugating strategems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.