Abstract

An experimental investigation of R410A condensation outside a horizontal smooth tube, a herringbone tube and a newly developed enhanced surface EHT tube has been conducted. The herringbone tube has a fin root diameter of 11.43 mm, a helical angle of 21.3 °, 48 fins with a fin height of 0.262 mm and an apex angle of 36 °, the EHT tube has an outer diameter of 11.5 mm with special structure, while the smooth tube has an outer diameter of 11.43 mm. Experiments were taken at a constant saturation temperature of 45 °C, a constant inlet vapor quality of 0.8 and a constant outlet vapor quality of 0.1; mass flux ranging from 5 kg/(m2.s) to 250 kg/(m2.s). Those tubes have different heat transfer performance at different mass flux. The EHT tube has the least heat transfer coefficient than the other two tubes at a low mass flux, while at a high mass flux, the enhanced tubes have a better heat transfer performance than the smooth tube. Heat transfer performance combined with pressure drop measurements reveal that the herringbone tube generally has a better heat transfer performance than the EHT tube, pointing out the herringbone is a wise choice for shell side condensation instead of the EHT tube. Characteristic analysis is made to account for various phenomena in this series of experiments.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call