Abstract

The need for reliable measurement of droplet velocities and droplet size has increased with the more widespread use of water mist systems. Two optical measuring techniques have been investigated, Particle Image Velocimetry (PIV) and phase Doppler anemometry (PDA). Measurements have been performed on two high-pressure nozzles, a hollow cone nozzle and a full cone nozzle. Both methods performed well close to the nozzle and further away from the nozzle. In the intermediate region the results obtained with PIV are biased against the larger droplets. The two methods complement each other, PIV giving the instantaneous velocity field and PDA giving both the droplet velocity and droplet size at a point. The measurement indicates that higher throw length can be archived with a full cone nozzle compared to the hollow cone nozzle, if both nozzles have the same cone angle and flow rate.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.