Abstract

In this study, the heat and mass transfer characteristics of desiccant coated heat exchanger (DCHE) and conventional heat exchanger are compared by experiments. A general-purpose test platform is built to test and compare the characteristics above. Based on the designed experimental setup, two heat exchangers of different depths of fins conventional/desiccant coated are experimentally investigated and compared with the given performance evaluation standards. In addition, parametric influences of inlet air velocity, hot water temperature and cycle time are analysed. Experimental results show that compared with the conventional heat exchanger, the heat transfer capacity of DCHE is reduced by 30% because of the heat resistance produced by desiccant coating. Pressure drop and Euler number are both increased by 60% approximately for the same reason. Doubling the depth of fins increases the average moisture removal by 40% and COPth by 10%, without changing the other structure parameters.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.