Abstract

The purpose of the present study was to compare the effectiveness of coagulation process conducted using a classical nonhydrolyzed coagulant—aluminum (VI) sulfate and pre-hydrolyzed coagulants: PAX XL 19H and Flokor 1.2A. Water samples subjected to coagulation were collected from selected water treatment plant after the pre-ozonation process. Research has been conducted in the winter season. True color of water amounted to 7.0 mg Pt/L and turbidity was 7.29 NTU. The study in a laboratory scale was carried out with the usage of a six-beaker flocculator. Volumetric coagulation was performed in water samples of the volume of 1 L. In six beakers, rapid mixing (3 min at the rotational speed of 200 rpm) was followed by 30 min slow mixing (at 30 rpm). After coagulation, the samples were subject to 60 min sedimentation. The coagulant dose was optimized for minimum color, turbidity, and UV254 absorbance values using conventional jar testing procedures. The optimum dose for aluminum (VI) sulfate amounted to 2.2 mg Al/L. For prehydrolyzed coagulants, the doses were much lower, i.e. 1.2 mg Al/L. Also less wear of water alkalinity was obtained than in the case of aluminum (VI) sulfate. The effectiveness of removal of turbidity for ALK, PAX XL 19H, and Flokor 1.2A was 63, 70, and 74% respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.