Abstract

This work aims at comparing results obtained from the DC Ramp test with the DC step test on the stator insulation of large hydro generators. Four cases of field measurements done on hydro generators are presented. Results are analyzed according to analytical solutions presented by the authors in recent publications for both methods. Quantities such as IR, PI, absorption current parameters and leakage currents are tabulated for each case and various aspects regarding respective advantages and complementarities pertaining to each method are discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.