Abstract

AbstractThe objective of this study was to assess lead release in a pipe rig system that was disinfected with either chloramines or free chlorine. The study was carried out using pipe loops and copper pipe rigs that had lead solder, which provided the only source of lead. The water quality of the treated water had a low alkalinity (<5 mg/L as CaCO3), neutral pH, and low hardness (<5 mg/L as CaCO3). However, the study used a corrosion control program that consisted of dosing with 0.8-mg PO4/L of zinc orthophosphate and controlling the pH to 7.3, that was consistent with the corrosion-control program operated in the host water treatment plant. Key findings from the study confirmed that chloramines would result in lead release under the current corrosion-control program, whereas free chlorine was not as compromising. Lead concentrations were approximately an order of magnitude lower in the free chlorine system than the chloramine systems. In this study, chloramines with a target residual concentration of 5...