Abstract

A design of a fully composite pylon with external grounding down-leads has been proposed for new-generation 400 kV transmission towers, able to save lines corridors and to reduce visual impact. This paper investigates and compares the backflashover performance of a composite pylon and two conventional metallic towers, which have been widely installed in Denmark. The transient models of overhead lines and all three towers were established respectively and the transient analysis was carried out in PSCAD. Monte Carlo method was used to estimate backflashover rate. The backflashover rate of composite pylon is 0.4526 cases per 100 km per year, which is in the same range, but slightly higher than that of metallic towers. The separated grounding down-leads of double circuits on composite pylon eliminates the danger of simultaneous backflashover of double circuits, which exists in transmission lines supported by metallic towers. After comparing the overvoltages to three phases of the three towers from backflashover, it is worthy considering that the installation of surge arresters at all three phases of composite pylon has a strong impact on the backflashover rather, but for the two metallic towers only the surge arresters at the upper phase has an impact.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.