Abstract
This paper presents a comparison of two of the most sensitive methods to detect low-level turn-to-turn faults in the windings of three-phase transformers. The performance of the negative sequence component and of the space-vector protection algorithms is tested under several internal and/or external fault conditions. The results indicate that the space-vector approach is slightly more sensitive for detecting low-level turn-to-turn winding faults. For more severe defects, the fault detection sensitivity of both methods is similar.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.