Abstract

Air-conditioning (AC) system is typically used to remove the sensible and latent heat loads in buildings. It provides cool and dehumidified air to meet the occupants comfort and good indoor air quality (IAQ). Improper design and analysis of AC process resulted in high cooling energy and unsatisfied indoor humidity level in tropical climate. The objective of this study is to identify the cooling energy in hotel restaurant by comparing the design with proper fresh air ventilation design. The hotel restaurant was designed with primary air unit (PAU) and air handling unit (AHU) as to remove sensible and latent loads. The performance of the AC system has been monitored and analysed using psychrometric chart. For the AC air side system, 296.2 kW of cooling energy was used in standard operation. An alternative design was proposed for the said hotel restaurant employing only one AHU, with a cooling capacity of 165.9 kW which was 43 % lower than the existing system. The difference in temperature, humidity ratio and air flow rate influenced the cooling energy for AC system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.