Abstract

In this study, a solar ejector cooling system is theoretically analyzed to evaluate refrigerants and determine their performance characteristics and environment-friendly nature for a fixed ejector geometry under a set of standard operating conditions. The results show that the refrigerant R1234yf is the best choice for the cycle, and is an environment-friendly refrigerant with thermo-physical properties similar to that of R134a. Moreover, it has a high entrainment ratio and is cheap when compared to other refrigerants, nonflammable, and safe. The results indicate that the cooling cycle COP increases during the day hours as the generator temperature increases and reaches a maximum value of 0.59 at an optimum generator temperature of 86 $${^{\circ }}$$ C in the middle of the day. The overall efficiency of the system varied in the range 38–45%. Furthermore, it was found that increasing the generator pressure by 40% reduced the COP by 58.5% and increased the critical backpressure by 27.3%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.