Abstract

This paper presents a performance comparison of a variable capacity Air Source Heat Pump (ASHP) and a horizontal ground loop Ground Source Heat Pump (GSHP). Both these systems were installed side-by-side at the Archetype Sustainable Twin Houses at Kortright Center, Woodbridge, Ontario, Canada. The heat pumps were tested in both heating and cooling modes for extreme weather conditions of Ontario. For cooling mode, the coefficient of performance (COP) of ASHP ranged from 4.7 to 5.7 at an outdoor temperature of 33 °C and 16 °C respectively, while the COP of GSHP ranged from 4.9 (at an ELT of 8.5 °C and EST of 19.2 °C) to 5.6 (at an ELT of 12.4 °C and EST of 17.8 °C). For heating mode, the COP of ASHP ranged from 1.79 to 5.0 at an outdoor temperature of −19 °C and 9 °C respectively, while the COP of GSHP ranged from 3.05 (at an ELT of 44.4 °C and an EST of 2.7 °C) to 3.44 (at an ELT of 41.5 °C and an EST of 5.48 °C). Data extrapolation and TRNSYS simulation were also performed to predict annual performances of each system for major Canadian cities.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.