Abstract

Comparative investigations of the conventional analog and optical communication analog fire detector signal attenuations with various numbers of fire detectors were performed in this research. The conventional fire detector signals with 1, 2, 16 and 32 fire detectors were 4.5, 4.0, 2.2 and 0.8 V, respectively. The fire detector signals were drastically decreased with the increase of the number of fire detectors. However, the optical communication fire detector signals were not changed with increasing the number of fire detectors. Therefore, optical communication fire detector system is a promising fire detection system for eliminating the false alarms.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.