Abstract
Uncertainties of renewable energy sources like wind power are one of the considerable challenges of prosumer microgrids. To meet the grid codes requirements regarding the voltage stability of wind farm integration, finding the balance between providing the demanding dynamic performance of the voltage and reactive power, and at the same time decreasing the investment on centralized reactive power compensation device, becomes an important research topic. This article compares the effects of the static synchronous compensator (STATCOM) and static VAR compensator (SVC) on transient voltage stability at the point of common coupling (PCC) of a doubly fed induction generator (DFIG)-based wind farm. And a new fast coordinated control scheme of STATCOM and DFIG is proposed for minimizing the capacity of centralized reactive power compensation device and making the best use of the reactive power control capability of DFIG. The simulation results based on test system show that STATCOM, even with less capacity, can contribute more reactive power than SVC for voltage stability, especially during the serious voltage drop transient stage, and perform a faster voltage recovery time after fault than SVC, proved to be a more economic choice; The proposed coordinated control scheme can not only improve the transient voltage stability, but also help reducing the capacity of STATCOM, so that the cost of investments in wind farms would be reduced.
Highlights
Renewable wind energy has been developed rapidly and it becomes the third electricity source of China
When the doubly fed induction generator (DFIG) feeds into a weak power system, the Qref can set to a non-zero value so that rotor-side converter (RSC) can provide reactive power to support the voltage. idref and iqref can be used to obtain udref and uqref, respectively
Strategy A: the DFIG operate in unity power factor; Strategy B: the DFIG
Summary
Renewable wind energy has been developed rapidly and it becomes the third electricity source of China. Literatures [7,8,9] show that STATCOM providing dynamic reactive power support, the system voltage can be established shortly after grid fault, and the transient voltage stability will be improved. Researches [15] and [16] only consider the coordination between the RSC and GSC of DFIG for voltage regulation and reactive power support. A new coordination method is proposed for reactive power control of DFIG and STATCOM, the RSC, the GSC and STATCOM supplying reactive power to the grid coordinately, and the DFIG is fully utilized and prior to activating the STATCOM.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.