Abstract

This paper presents the comparative improvement of the voltage profile of the distributed power system using a Dynamic Voltage Restorer (DVR) and a Distributed Static Synchronous Compensator (D-STATCOM). The IEEE benchmark 13-bus distributed power system is used to present the distributed power grid. A proposed DVR is connected in series with bus 632 while a D-STATCOM is connected in parallel with bus 632. Comparative simulation results of the system with DVR and D-STATCOM are performed by using commercial MATLAB software. It can be concluded from the simulation results that DVR is suitable to mitigate the voltage sag of the load side while D-STATCOM can enhance the voltage stability margin of the buses that are located near the connected bus of the proposed D-STATCOM in the distributed grid.