Abstract

Results are reported of comparative measurements made in 14 HV (high-voltage) laboratories in ten different countries. The theory of the proposed methods of characterizing the dynamic behavior is given, and the parameters to be used are discussed. Comparative measurements made using 95 systems based on 53 dividers are analyzed. This analysis shows that many of the system now in use, even though they fulfil the basic response requirements of the standards, do not meet the accuracy requirements. Because no transfer measurements were made between laboratories, there is no way to detect similar errors in both the system under test and the reference system. Hence, the situation may be worse than reported. This has led to the recommendation that comparative measurements should be the main route for quantifying industrial impulse measuring systems. >

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.