This paper provides information on laboratory performance of 15 and 35 kV premolded joints from three manufacturers. Data on partial discharge, ac and hot impulse voltage breakdown tests, and dissection of breakdowns are presented for joints that were tested immediately after their assembly and after one year aging immersed in room temperature water (15-30degC), under operating voltage. The test program was repeated twice using joints acquired with a two-year interval. The two batches showed similar performance indicating that all three manufacturers provide consistent quality joints. AC breakdown strength of the joints practically did not change with aging. In contrast, their impulse breakdown strength decreased noticeably. Joints having partial discharge levels up to 5000 pC were included in the study. No obvious correlation was found between the presence of partial discharge and the joints ultimate dielectric strength.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.