Abstract
This study presents a comparative analysis of two different interphase reactors (IPRs) applied in a 36-pulse diode rectifier. One is traditional triple-tapped IPR; the other is unconventional IPR (UIPR) composed of the primary winding and secondary winding. The primary winding is double-tapped conventionally and the secondary winding is connected with a single-phase full-wave rectifier. The operation modes and optimal parameters of both IPRs are analysed. The effect of different operation modes on output currents of the two three-phase diode-bridge rectifiers, input currents and load voltages is also analysed. Under the optimal parameters, both rectifiers operate as 36-pulse diode rectifiers and reduce the total harmonic distortion of input line currents to be 5%. Especially, the proposed rectifier using UIPR is easy and simple to implement. Some experiments are provided to validate the theoretical analysis.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.