Abstract

The paper presents results of comparative analyses of optical signals generated by corona discharges occurring in the vicinity and on the surface of power transmission lines made of five different materials under laboratory conditions. Three aluminium-based materials were chosen: pure aluminium, aluminium with added magnesium, and aluminium with added silicon, and for comparison purposes also, steel-based lines were considered: copper-coated steel and steel with added chromium and nickel. A three-phase triangular arrangement system operating under maximal voltage equal to 110 kV was applied for experimental tests. The optical radiation was registered using a spectrophotometer. During research works, also the influence of corona generation voltage and distance between power lines was investigated. Based on the achieved results, it was stated that the highest corona intensity was found for aluminium-based lines, for both pure aluminium and aluminium with added magnesium and silicon. The lowest corona intensity was observed for chromium- and nickel-alloyed (stainless) steel.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.