Abstract

In a compact closed two-phase loop thermosyphon which consists of a multiradiator and a refrigerant bath with multiple power modules mounted vertically, the heat radiation performance deteriorates as the refrigerant bath becomes thinner. We have found that this is because the return condensate is blocked by the back flow of the bubble in the return path when the heat load decreases and increases sharply. We have also improved the heat radiation performance by providing an adiabatic path between the boiling area and the return path.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.