Abstract
Abstract : Compact fluorescent (CF) lamps, which are available as an energy-efficient replacement for ordinary incandescent light bulbs, can be used in a variety of fixture types, including existing incandescent, ceiling-mounted, recessed downlights. However, CF lamps are not shaped or sized identically to the incandescent bulbs being replaced; therefore, light distribution will be changed by these retrofits. Army facilities have numerous incandescent downlight fixtures that are candidates for compact fluorescent retrofits. The information in this study can provide guidance for selecting appropriate retrofits. This study examined the photometric effects of installing several types of CF lamps in several types of incandescent downlight fixtures. Test results show that, for shallow depth fixtures, several types of CF lamps perform adequately. For deeper fixtures using nonreflective baffle rings, retrofitting with some CF lamps causes light output from the fixture to drop drastically. CF retrofits also caused a wider pattern of light distribution and increased luminance values. Changes in distribution and luminance need to be considered by Army facility managers contemplating CF retrofits. (MM)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.