Abstract
During two legionellosis outbreak investigations, one at a geriatric centre and the other in high-rise housing for seniors, it was observed that additional cases of legionellosis occurred in nearby smaller residential settings. This apparent geographical cluster of legionellosis occurred in the same general area of a community water storage tank. No potential airborne sources in or near the area could be identified, but a community water system storage tank that was centrally located among case residences spurred an investigation of water-quality factors in the identified investigation area. Conditions conducive for Legionella growth, particularly low chlorine residuals, were found. The rate of legionellosis among residents aged ⩾50 years in the investigation areas (61·0 and 64·1/100 000) was eight times higher than in the rest of the service area (9·0/100 000) and almost 20 times higher than the statewide annual average incidence rate (3·2/100 000). A water mains flushing programme in the area was launched by the water utility, and water samples taken before and during flushing found L. pneumophila.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.