Abstract

Qatar tops the world in per capita CO2 emissions and per capita total primary energy supply. Adaptive comfort standards and thermal comfort field survey data are not available for Qatar. We conducted a thermal comfort survey in Doha, Qatar, for five summer months in 2016. In nine typical randomly selected air-conditioned office buildings, 828 subjects returned 1926 questionnaires. We found 24.1°C as Griffiths comfort temperature. Subjects mostly felt cooler sensation (mean: −0.23). Fanger’s Predicted Mean Vote always overestimated the actual sensation. We recorded very low to near still air conditions in all the indoors (mean speed: 0.04m/s.) While 39.1% occupants felt neutral, 72.1% voted in the central band of the sensation scale and 85% accepted the environments. The occupants adapted through clothing. Clothing insulation significantly varied with air temperature. Public buildings are significantly cooler than the private buildings, and yet are less acceptable throughout the survey.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.