Abstract

The air conditioning method based on radiation heat exchange has the characteristics of small vertical temperature gradient, high thermal comfort and energy saving, and has become a hot spot of attention. The Fluent numerical simulation, the experiment in this paper studies the direct expansion multi-line radiant air conditioner under the artificially simulated climate environment in winter heating, summer cooling and dehumidification. The temperature difference of the radiation + fresh air mode at the same time indoors under heating conditions is less than 2.5 °C, and the time to reach the indoor set temperature of 24 °C is about 2–3 h. Under cooling conditions, the temperature difference of the radiation + fresh air mode at the same time in the room is about 0.5–2 °C, and the time to reach the indoor set temperature of 26 °C is about 1–3 h. In the fresh air mode, the indoor temperature difference and response time at the same time are slightly larger than the radiation + fresh air mode. The freezing and dehumidification effect of fresh air is obvious, the moisture content of dehumidifying fresh air is between 6.3 and 10.5 g/kg, and the dehumidification efficiency can reach 50%. Under the same artificial simulated climate environment, the consumption of the three modes is not much different. When the outdoor temperature in heating conditions is higher than 9 °C, the fresh air mode can get better, and the radiation + fresh air mode can achieve better comfort when running indoors under various conditions.