Abstract
A heating system that combines a ground source heat pump and solar collectors with a combistore was measured in detail in the laboratory by means of “whole system testing”. The test rig thereby emulated a building with floor heating, hot water tappings, flat plate solar thermal collectors and a ground source heat exchanger. The tested heating system covered the heat demand for space heating and domestic hot water preparation in a reliable way with a good annual system performance factor of 4.5 that was determined after the physical test by means of test-calibrated simulation models. Nevertheless the measurements revealed that there is still room for improvements. It was found that the heat pump operates in space heating mode in an oscillating on/off behavior with short runtimes and respectively with a high number of starts and in addition with a supply temperature that is in average 8K above the temperature that is needed in the heat distribution. Furthermore a significant transport of energy, from the upper part of the store that is reserved for domestic hot water preparation to the lower part, reserved for space heating, was detected.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.