Abstract

This article studies the potential combination of direct ground cooling (DGC) with district heating (DH) and ground source heat pumps (GSHP) to compare the required borehole depths and needed drilling areas. It also examines two different borehole sizing approaches to optimize investment costs and drilling areas. The results show that the required borehole depths in most cases are shorter for the DGC and DH combination than for the DGC and GSHP combination. It is also demonstrated that the optimal range of borehole outlet temperatures could be chosen based on the trade-off between borehole installation and terminal units’ costs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.