Abstract

It is analyzed, if and to which share the deep borehole heat exchanger (BHE) at RWTH Aachen University in its current state is capable of heating an office building located at its top, called SuperC. Furthermore, possible modifications to the BHE and to the hydraulic connection to the building's heating system are discussed.Models of the BHE and of the building are each validated with measurement data and than connected to each other to carry out system simulations for one heating period. It is found that the BHE in its current state can support the heating system by a notable share of the annual heating demand by supplying the low temperature heating systems of the building. An alternative system configuration and a different inner BHE pipe provide the opportunity of higher supply temperatures leading to a higher fraction of geothermal heating.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.