Abstract

The Katowice Fair Building in Poland collapsed on 28 January 2006. It was a steel building having dimensions 96.360 × 102.875 m in the general plan. The roof was constructed from truss elements, supported on 6 internal and 66 external columns situated along external walls. The results of engineering investigations on the reasons of total collapse of Katowice Fair Building structure has presented herein. Generally the collapse occurred as a consequences of: incorrect arrangement of the structure, unsufficient strength and rigidity of main structural elements, and finally of the overloading action of thick ice – snow layer. The following parameters have been estimated: the reliability model of the structure system, arrangement of bracings, construction of main columns, main girders and supporting, field connections of elements and shaping of the roof surface.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.