Abstract
Exponent Failure Analysis Associates was retained by a municipal government to perform an independent study of a fatal collapse in a local sewer treatment plant. The reinforced concrete dome shell covering a cylindrical prestressed concrete digester tank collapsed due to sludge overfilling. The collapsed dome, similar to domes on two adjacent identical tanks, showed radial and circumferential cracking prior to the collapse. Analysis showed the dome cracks were a result of temperature and shrinkage stresses, and of internal overpressure happening at some time prior to the overpressure resulting in the collapse. Inspections of the postfailure debris and analysis of the dome cracking preceding the collapse show practically no relationship between the dome condition prior to collapse and the failure. Failure of the sludge level monitoring system and the lack of a sludge overflow system are cited as the primary reasons for the failure.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.