Abstract

This paper proposes a co-estimation and resilient compensation control framework for multi-area load frequency control (LFC) systems in the presence of false data injection (FDI) attacks and denial-of-service (DoS) attacks. To relax the requirement on existing DoS attack models, which are usually considered under the assumption that both its frequency and duration are constrained, a new DoS model within a known bounds of the sleeping and active period of the attack signal is proposed. The injected FDI attack signal is generated by an external dynamic systems. A switching impulsive observer and a switching state observer are constructed to estimate the unknown FDI attack signal and the system state, respectively. Moreover, a new exponential stability criteria of the output feedback multi-area LFC systems under DoS and FDI attacks is first derived by using attack parameter dependent time varying Lyapunov function method. Then, a co-design method of a resilient attack compensation controller, state estimator, and attack estimator is developed. Finally, case studies are considered for verification of the effectiveness of the proposed theoretical results.