Abstract

In order to save more energy and quicken the load change speed of air-cooled steam condenser units, the closed-loop optimized control on the fan speed is proposed and its realization is worth making intensive study. In this regard, the study presents the static and dynamic models of air-cooled steam condenser, and the characteristics of turbine power output affected by fan speed. Then, the structure of closed-loop control on fan speed is designed. Furthermore, two optimized methods on condenser pressure based on fan speed control are separately discussed: the optimum condenser pressure is solved by the genetic algorithm to save more energy, and the condenser pressure regulation is combined with traditional boiler-turbine coordinated control to accelerate the load response. Case study in our paper proves that the fan speed optimization can significantly improve the unit load-following capability, and furthermore unit coal consumption has been significantly reduced when the unit operating in a stable load condition.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call