Abstract

Standby generation systems in low- and medium-voltage applications connect to the utility power system in a number of different ways. Typically, an automatic transfer switch is a part of most power system connections. Engineers can choose three- or four-pole transfer switches for the intertie point. The application's sensitivity to a power interruption during switching helps determine transfer-switch selection. The transfer switch can be contactor or circuit breaker based, or it can be a bypass design. At medium voltage, special requirements must be considered. Ultimately, the correct arrangement must be chosen depending upon grounding locations and neutral bonding. Incorrect power system bonding and grounding can cause unwanted transients or hazardous multiple grounds (improper ground-fault protection) depending upon the transfer-switch selection. Improper design can create unintentional current paths and defeat ground-fault protection. A transfer switch must be chosen for robust operation and maintenance at the beginning of the design process.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.