Abstract
This study applies the k nearest neighbour (kNN) regression to ascertain optimal operating strategies for a chiller system, hence lowering its carbon emissions. First, 19 operating variables were identified for the regression of the coefficient of performance (COP)—the total cooling capacity divided by the total power of system components. Cross validation involved splitting ten partitions of test samples from a set of operating data with 14537 time points. The optimal k = 3 is evaluated with the lowest mean square error of 0.00148. Using the random kNN, the most significant variables are found to be the temperature and flow rate of return chilled water, the load of individual chillers is the next, followed by the condenser water leaving temperature in system optimization. Based on the existing building cooling load profile with ambient conditions, the optimal variables with the maximum COP are identified from neighbour conditions at the 99th percentile of the distance distribution. The optimal schedule of switching chillers and temperature settings improve the seasonal COP from 3.27 to 3.90, reducing the carbon emissions by 178160 kg CO2e. The novelty of this study is the application of the kNN regression with enhanced distance selection criterion to identify specific optimization strategies which fulfil the existing design and operating constraints of engineering systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.